Voltage Drop Calculator

Voltage drop for copper and aluminum wire, and the smallest size under 3%.

  • Free, no sign-up
  • Updates as you type
  • Works on your phone
  • Updated
Try an example:20 A circuit, 100 ftShed feed, 240 V 40 A 150 ftEV charger, 240 V 40 A 60 ft12 V lights, 30 ft480 V 3-phase motor
Circuit
Wire
Voltage drop——
Voltage at the load
—
Smallest wire for drop and amps
—
This wire's ampacity
—
Smallest wire for target drop
—
Smallest wire for 5%
—
Max length at target
—
Power lost in the wire
—

    Compare wire sizes

    Lime bars meet your target. The dark bar is the size you picked.

    Voltage Drop Calculator by dasaas. Free tools for everyday work.

    Quick answer

    Voltage drop = 2 × amps × ohms per 1,000 ft × one-way feet ÷ 1,000 (use 1.732 instead of 2 for three-phase). For a 16 A load on 50 ft of 12 AWG copper at 120 V, the drop is 3.2 V, or 2.6%, which is under the 3% the NEC recommends for branch circuits.

    For planning only. Uses DC resistance at 75°C from NEC Chapter 9, Table 8 (AC circuits in steel conduit run slightly higher) and NEC Table 310.16 ampacities for 30°C ambient with no more than three current-carrying conductors, before any derating. Electrical work must follow your local code and may require a licensed electrician.

    How voltage drop is calculated

    Every wire has resistance, so some voltage is lost between the panel and the load. The loss grows with current and length and shrinks with larger wire. This calculator uses the DC resistance at 75°C published in NEC Chapter 9, Table 8:

    Resistance of common copper wire

    SizeSolid (Ω per 1,000 ft)Stranded (Ω per 1,000 ft)
    14 AWG3.073.14
    12 AWG1.931.98
    10 AWG1.211.24
    8 AWG0.7640.778
    6 AWG—0.491
    4 AWG—0.308

    Questions people ask

    What is an acceptable voltage drop?

    Informational notes in the National Electrical Code recommend no more than 3% on a branch circuit and 5% for the feeder and branch circuit combined. They are recommendations, not requirements, but following them keeps lights and motors working properly.

    How do you calculate voltage drop?

    For single-phase circuits, voltage drop = 2 × current × resistance per foot × one-way length. For three-phase, replace 2 with 1.732 (√3). Resistance comes from NEC Chapter 9, Table 8.

    Should I enter the one-way or round-trip length?

    Enter the one-way length from the panel to the load. The formula already accounts for the current going out and back.

    What size wire do I need for 100 feet?

    It depends on the current and voltage. At 120 V and 16 A, 100 ft of stranded copper needs 8 AWG to stay under 3%: 12 AWG drops about 5.3% and 10 AWG about 3.3%. Enter your circuit to see the smallest size that works.

    Does this tell me what size wire I need?

    It shows the smallest wire that both keeps voltage drop within your target and is rated for the current under NEC Table 310.16, including the 15, 20 and 30 A breaker limits for 14, 12 and 10 AWG copper (240.4(D)). It does not apply derating for hot locations or bundled cables, so check those with an electrician.